What size earth wire for house wiring in Pakistan?

PILONE CABLES TECHNICAL TEAM

Updated 19 August 2026

Match the earth to the line. Up to 16 mm², the earth wire is the same size as the live wire it runs with.

A 1.5 mm² light circuit takes a 1.5 mm² earth, a 7/29 socket circuit takes a 2.5–3 mm² earth, and a 4 mm² AC point takes a 4 mm² earth. A 16 mm² earth covers line sizes from 16 up to 35 mm², and above 35 mm² the earth may be half the line size. The easiest way to get this right in a house is 3-core cable — the third core is the earth, already at the correct size.

What does the earth wire in a house actually do?

Every circuit in the house has a live wire that carries current in and a neutral that carries it back. The earth wire carries nothing in normal use. It connects every metal part a person can touch — the geyser tank, the AC chassis, the washing machine body, the earth pin of every socket — to the ground itself. The day insulation fails and a live conductor touches a metal case, the earth gives that fault an easy path away, the current jumps, and the breaker trips in a fraction of a second. Without an earth, the case simply sits at 220 V and waits for a hand.

That is why the earthing cable size in Pakistan is set by the wire it protects, not by the load on the circuit. The earth never carries the appliance's current; it carries the fault current, which for that fraction of a second can be far larger than anything the circuit sees in normal service. So the earth is sized against the live conductor — and the rule for doing it is short enough to memorise.

Earth wire size for house circuits, size by size

In Pakistani house wiring, the minimum earth wire size follows the line conductor it protects. Up to 16 mm², the earth conductor is the same size as the line conductor. From 16 mm² up to 35 mm², a 16 mm² earth is enough, and above 35 mm² the earth may be half the line size. So a 1.5 mm² light circuit takes a 1.5 mm² earth, a 2.5–3 mm² socket circuit — the wire Pakistani shops sell as 7/29 — takes a 2.5–3 mm² earth, a 4 mm² air conditioner circuit takes a 4 mm² earth, and a 25 mm² or 35 mm² submain takes a 16 mm² earth. That is the tabulated convention BS 7671 uses when the earth conductor is the same metal as the line conductor; an electrician can calculate a smaller size from fault current and disconnection time, but the sizes above are the safe default.

Minimum earth conductor against line size, per the tabulated convention BS 7671 frames for an earth of the same metal as the line: equal to the line up to 16 mm², 16 mm² for lines over 16 up to 35 mm², half the line above 35 mm². An adiabatic calculation from fault current and disconnection time can justify a smaller earth — that is design work, not a chart. Trade codes are the imperial strand names Pakistani shops sell by; conductor data per IEC 60228. Verify the earthing design with a licensed electrician.
Line wireTrade codeMinimum earthWhere you see it
1.5 mm²3/.0291.5 mm² — same as lineLight circuits
2.5–3 mm²7/.0292.5–3 mm² — same as lineSocket circuits
4 mm²7/.0364 mm² — same as lineAC points
6 mm²7/.0446 mm² — same as lineGeyser, stove, small submains
10 mm²7/.05210 mm² — same as lineFloor submains
16 mm²7/.06416 mm² — same as lineMains and meter tails
25 mm²16 mm²Larger submains
35 mm²16 mm²Main incomer

Read the third column as a floor, not a target — an earth bigger than the minimum is never a fault, an earth smaller than it always is. And note what the rule implies for shopping: for every final circuit in a house, the earth is simply another core of the same wire, which is why 3-core cable such as 4mm 3 core standard cable solves the question by construction. Choosing the line sizes themselves is the other half of the job — that is the best wire for house wiring guide.

Earthing wire size with breaker rating

A breaker never sizes the earth directly. The breaker protects the live wire, so the live wire must be rated above the breaker; the earth then follows the live wire by the rule above. The chain is breaker → line → earth, and for the circuits a Pakistani house actually has, it lands like this.

Typical pairings for a 220 V single-phase Pakistani house. Line capacity is for two loaded conductors, copper, PVC, per BS 7671 reference method C (clipped direct) at 30°C ambient, before derating for conduit, grouping or high ambient — the derated figure is what must stay above the breaker. Conductor data per IEC 60228. Earth minimum per the same-size convention up to 16 mm². Verify with a licensed electrician for your installation.
MCBCircuitLine wireLine capacityMinimum earth
10 ALights1.5 mm² (3/.029)19.5 A1.5 mm²
16 ASockets, short surface runs2.5 mm² (7/.029)27 A2.5–3 mm²
20 A1.5 ton AC point4 mm² (7/.036)36 A4 mm²
32 A6 kW geyser, electric stove6 mm² (7/.044)46 A6 mm²
40 AFloor submain10 mm² (7/.052)63 A10 mm²
63 AMain switch and tails16 mm² (7/.064)85 A16 mm²

Two things follow from the chain. First, when a long run forces the line up a size for voltage drop, the earth goes up with it — the rule tracks the wire actually installed, not the breaker. Second, the table assumes the breaker matches the line in the first place; a 20 A breaker on 1.5 mm² wire is a fault of its own, and the wire size too small guide shows how it ends.

Earth wire or earth rod — which one are you buying?

A house earthing system is two different purchases, and they get confused on the phone daily. The earth wire — green or green/yellow insulated copper — runs with the circuits and gathers every metal part onto one conductor. The earth rod is the electrode: a rod driven into the ground in a pit near the meter, commonly packed with salt and charcoal in Pakistani practice, that gives the fault its final exit into the soil. We manufacture the wire; the rod, the clamp and the pit materials come from the hardware market.

The run from the distribution board to that rod — the main earthing conductor — follows the same sizing rule, applied to the biggest line conductor in the house: the meter tails. Tails of 10 mm² take a 10 mm² earth, tails of 16 mm² take 16 mm², and 25 or 35 mm² tails take 16 mm² under the over-16 rule. Pakistani practice often runs 6 mm² to the rod on a 10 mm² main — an adiabatic calculation can justify it, and the marla cable lists reflect that practice — but the tabulated size is the conservative default. That is why most houses land between 6 and 16 mm² for the rod run, and it is the job our earth cable range — 6, 10 and 16 mm², up to 35 mm² — is drawn for.

A solar array on the roof raises its own earthing questions — panel frames, inverter, the DC side — and has its own guide: solar earthing cable size.

Why does "earth through the conduit" fail?

A shortcut some wiring jobs take: skip the earth core and let the conduit carry the fault — the pipe is metal, the theory goes, and it reaches every box. It fails for reasons visible on any site. Most house conduit in Pakistan is now PVC, which is an insulator: there is no path at all, only the look of one. Where the conduit really is steel, the path depends on every threaded joint staying tight, unpainted and unrusted for the life of the building, and it breaks silently the day a coupling is disturbed or a plastic box is spliced into the run. Nobody tests it afterwards, so nobody knows.

The other version of the shortcut is the empty earth pin — 2-core cable run to a 3-pin socket. The socket looks finished, the earth terminal connects to nothing, and every metal-bodied appliance plugged in there is floating. An earth is a continuous copper conductor of its own, terminated at both ends, all the way from the appliance to the rod. Anything less is a drawing of an earth.

Worked example: what earth does a 7/29 socket circuit need?

Take the commonest circuit in the country: sockets wired in 7/29 — seven strands of 0.029 inch, which computes to about 3.0 mm² and is sold as 2.5–3 mm². The line is under 16 mm², so the earth matches it: 2.5–3 mm², which in practice means the same 7/29 in green/yellow from the general wiring range, or the third core of a 3-core cable.

The size matters because the earth is half of the fault loop. Taking the 2.5 mm² class 2 figures, resistance is 7.41 Ω/km, so a 20 m run puts 20 × 7.41 ÷ 1000 = 0.148 Ω in the live leg and, with a matching earth, the same 0.148 Ω in the return — 0.296 Ω of cable in the loop. Drop the earth one size to 1.5 mm² at 12.1 Ω/km and the return leg alone becomes 20 × 12.1 ÷ 1000 = 0.242 Ω, and the loop rises to 0.390 Ω — a third more. A higher loop resistance means a smaller fault current and a slower trip, and a fast trip is the entire reason the earth exists.

On a rod-earthed house the pit's own resistance sits on top of both figures, and usually dominates them — which is why the pit is maintained, not just dug, and why an RCD or ELCB in the board is worth having alongside the earth, never instead of it.

The sizes on this page are the tabulated minimums, stated with their assumptions. The exact earth size for an installation depends on fault current and disconnection time, and the earthing design is the rod, the wire and the bonding together. Have a licensed electrician verify the design before anything is buried or plastered over — and size the line conductors first with the cable size calculator.

Earth cable from the Lahore factory

For circuit earths up to 16 mm² the answer is usually already in the cable: take 3-core, or add a green/yellow single from the general wiring range at the same size as the line. For the main earthing conductor — the board-to-rod run — we draw a dedicated earth cable range, 6 to 35 mm², class 2 stranded copper, on the Pilone line in Lahore, from a family in the copper trade since 1992.

Factory-direct price — 6mm² earth cable
Contact for quote
Message us for today’s rate
WhatsApp for today's rate

Copper cable is priced off the day's copper rate, so we quote per metre and per coil on WhatsApp. Send the size, the metres and your city: Punjab in 1–2 days, rest of Pakistan in 2–4.

The other sizes: 10mm² earth cable and 16mm² earth cable for most house rod runs, 25mm² and 35mm² for panel and industrial earthing.

Frequently asked

Ghar ki earthing ke liye kitne mm ki tar chahiye?
Jitni moti live tar, utni hi moti earth — 16 mm² tak yehi qaida hai. Light circuit 1.5 mm², socket circuit 7/29 (2.5–3 mm²), AC point 4 mm². Meter se earth rod tak jaane wali main earth aam ghar mein 10 ya 16 mm² banti hai. 3-core cable lein to teesri core sahih size ki earth khud hoti hai.
Can the earth wire be one size smaller than the live wire?
Not below 16 mm². Up to that point the tabulated convention keeps the earth equal to the line, and a smaller earth raises the fault-loop resistance, cuts the fault current and slows the trip. Above 16 mm² the convention itself relaxes: a 16 mm² earth covers lines up to 35 mm², and above 35 mm² the earth may be half the line. A licensed electrician can calculate an exact minimum from fault current and disconnection time.
Is the green core in 3-core cable the same thing as earth cable?
Same job, two places. The green or green/yellow third core in 3-core cable is the circuit's earth, already matched to the live cores. The product sold as earth cable — single-core green/yellow, 6 to 35 mm² — is for the runs a 3-core does not cover: distribution board to the earth rod, panel earthing, bonding. A house normally needs both.
What size earth wire for an AC point?
4 mm², the same as the live wire — which is why the sizing guides say to run 3-core, so live, neutral and earth are all 4 mm² in one cable. On a 20 A breaker with a 4 mm² line, a thinner earth would be the weakest conductor on the circuit during the one event that matters. The full circuit sheet is in the 1.5 ton AC wire guide.
Do I still need an earth wire if the board has an ELCB or RCD?
Yes. An ELCB or RCD detects leakage current and disconnects fast, and it is worth having — but it is a switch, not a path. Without an earth, a live case does not leak anywhere until a person touches it; the device then trips during the shock, not before it. Earth and RCD work together: the earth makes the fault flow at once, the device clears it.
What is the earth cable price in Pakistan per meter?
It moves with the day's copper rate, so we quote on WhatsApp rather than publish a figure that goes stale. Send the size — 6, 10, 16, 25 or 35 mm² — the metres and your city to +92 319 4262451 and the factory answers with today's rate. Delivery is 1–2 days in Punjab, 2–4 in the rest of Pakistan.