Skip to content
Factory-direct from Lahore · Nationwide delivery in 2–4 days +92 319 4262451 WhatsApp

Which wire is best for house wiring in Pakistan?

PILONE CABLES TECHNICAL TEAM

Updated 19 August 2026

Single-core copper, sized per circuit: 1.5 mm² (3/.029) for lights and fans, 2.5 mm² (7/.029) for sockets, 4 mm² (7/.036) on its own 20 A MCB for each AC, and 6–10 mm² for the main from the meter to the board.

There is no single best wire for a whole house, because a fan circuit and an AC circuit carry different current — the size follows the circuit. What makes any of those wires "best" is full-gauge strands, pure copper and the right size for the job, none of which a brand slogan supplies. The whole table, with the amps behind it, is below.

What house wiring wire size does each circuit need?

A house is wired as separate circuits from the distribution board, and each circuit gets the size its load demands. The loads are simple arithmetic on Pakistan's 220 V supply: a 1.5 ton AC at 1500–1800 W draws 1500 ÷ 220 = 6.8 A up to 1800 ÷ 220 = 8.2 A; a geyser draws its plate wattage over 220 — 2000 W is 9.1 A, 4500 W is 20.5 A; lighting circuits sit under a 6–10 A breaker. Against those loads, this is the sheet:

Sizes for a 220 V single-phase domestic supply. Cable rating is the two-loaded-core figure per BS 7671, reference method C (clipped direct), 30°C ambient, copper, PVC; conductor data per IEC 60228. Derate for conduit, bunching and summer heat. Verify sizing with a licensed electrician for your installation.
CircuitSizeTrade codeCable ratingMCBWorked out in
Lighting and fans1.5 mm²3/.02919.5 A6 A3/.029 single core coil
Sockets and kitchen2.5 mm²7/.02927 A16 A7/.029 single core coil
AC point, one per unit4 mm²7/.03636 A20 A type C1.5 ton AC guide
Geyser, by plate kW2.5–4 mm²7/.029–7/.03627–36 A16–25 Ageyser cable guide
Meter to board (main)6–10 mm²7/.044–7/.05246–63 AMain switch, per total loadcable size calculator
Earth run to the rodsSame as the main — 6–10 mm²7/.044–7/.052earthing wire size guide

The best wire for house wiring in Pakistan is single-core copper, sized circuit by circuit: 1.5 mm² (the code shops call 3/.029) for lighting and fan circuits on a 6–10 A breaker, 2.5 mm² (7/.029) for socket and kitchen circuits on a 16 A breaker, 4 mm² (7/.036) on its own dedicated 20 A breaker for every air-conditioner point, 2.5–4 mm² for the geyser according to its plate wattage, and 6–10 mm² (7/.044 or 7/.052) for the main cable from the meter to the distribution board. On Pakistan's 220 V single-phase supply, those sizes carry every normal domestic load with margin left after derating. The capacities behind them are read per BS 7671, reference method C at 30°C, with conductors to IEC 60228. A brand name changes none of these numbers: full-gauge strands, pure copper and the correct size for each circuit are what make a house wire the best one.

On the main run, the arithmetic is worth seeing once. Two 1.5 ton ACs draw 2 × 8.2 = 16.4 A and a 3 kW geyser draws 3000 ÷ 220 = 13.6 A — that is 30 A before a single light or socket is counted, which is why the marla guides put 10 mm² (rated 63 A) on the meter run rather than 6 mm² (46 A). Planning a whole build rather than one circuit? The sequencing — when to buy, what the electrician quotes, what goes in before plaster — is on wiring for a new house.

Single core or 3/29 or 7/29 for house wiring?

This question, asked in every hardware bazaar, mixes two different choices. 3/29 and 7/29 are single-core wires — the codes name the strands inside one insulated core: 3 strands of 0.029 inch, or 7 of them. So "single core or 3/29" is not a choice at all. The real choices are the size for each circuit (the table above — 3/.029 works out to 1.28 mm², 7/.029 to 3.0 mm², and the full decode is in the strand codes guide) and the build of the conductor — solid, stranded or flexible:

Strand builds per IEC 60228. At the same nominal size, all three builds are read against the same current-capacity row (BS 7671, reference method C, 30°C, copper, PVC) — the build changes handling and termination, not the rating. Verify sizing with a licensed electrician for your installation.
BuildAt 1.5 mm²At 2.5 mm²In the wall
Solid (class 1)1 strand1 strandSits firm in screw terminals; stiff around conduit bends. Suits short, straight lighting runs.
Stranded (class 2)7/0.537/0.67The default Pakistani house wire — 7/.029 is this family; 3/.029 is a three-strand stranded build sold alongside it. Pulls through bends without fight.
Flexible (class 5)30/0.2550/0.25Easiest pull of all; fine strands must be twisted or ferruled at every termination or they stray at the screw.

Honest trade practice: most houses in Pakistan are wired in stranded class 2, and it is the right default — it handles the bends of a chased conduit run and terminates cleanly. Solid wire (1.5mm single core solid, 2.5mm single core solid) costs a little less to make and holds its shape in accessory terminals; plenty of electricians prefer it for lighting. Flexible in the wall is common too and carries the same current — just insist the electrician terminates it properly. The builds are compared at length in flexible vs solid cable, single core against multi-core sheathed cable in single core vs multi core, and the 3/29-against-7/29 decision has its own guide — the short version is that they are different sizes for different circuits, not competitors.

What does the "best" wire actually mean?

Every maker in the country calls its wire the best. Strip the slogans and three checks remain, and all three can be done at the shop counter:

Correct size for the circuit is the fourth test, and it is the one this page's table settles. Which company to buy from once a coil passes these checks — how the factories differ and what factory-direct changes — is a separate question with its own page. The size-to-code conversions for every gauge are on the wire size chart.

Where does house wiring go under-size?

The same few mistakes appear in house after house, and every one of them is a size decision made for the wrong reason:

A 5 marla circuit set, checked

Put the table to work on a real plan. A single-storey 5 marla house wires to 11 circuits: 3 lighting circuits on 1.5 mm², 3 socket circuits, 1 kitchen circuit and 1 pump circuit on 2.5 mm², 2 AC points on 4 mm², and 1 geyser circuit — with a 10 mm² main from the meter and a matching 10 mm² earth run. The coil counts and metre totals for that exact set are worked out in the 5 marla house wiring guide.

One check worth doing on any plan is the longest socket run — usually the kitchen. Suppose that run is 15 m from the board and the circuit is carrying 10 A. On 2.5 mm² the cable drops 18 mV per amp per metre, so the loss is 18 × 10 × 15 ÷ 1000 = 2.7 V — inside the 3.3 V half-share of a 3% budget on 220 V (6.6 V for the installation, half spent by the submain). Load the same run to its full 16 A breaker, though, and the drop is 18 × 16 × 15 ÷ 1000 = 4.3 V — over budget, which is why an unusually long, heavily loaded kitchen run sometimes goes up to 4 mm². Run your own lengths through the voltage drop calculator.

Other plot sizes have their own worked lists — 3 marla, 7 marla, 10 marla, 1 kanal — and the method behind all of them is on house wiring cable quantities.

Every capacity on this page is a clipped-direct figure at 30°C. In a Pakistani house the wire runs in conduit, bunched, through summers far above 30°C — derate for all three, per BS 7671, before trusting any margin. Have a licensed electrician confirm every size against your approved layout and load, or start with the cable size calculator.

The wire for this job

Coil of 7/.029 single-core PVC-insulated copper house wiring cable
7/.029 · 3.0 MM² · SINGLE CORE · 450/750 V

7/.029 Single Core Copper Cable

The socket wire of the house — seven full-gauge stranded copper conductors measuring 3.0 mm², PVC insulated to 450/750 V, drawn on the Pilone line in Lahore.

Factory-direct price
Contact for quote
Message us for today’s rate
WhatsApp for today's rate

Cable tracks the daily copper rate, so we quote per coil on WhatsApp. Send your circuit list and city — Punjab in 1–2 days, rest of Pakistan in 2–4.

The rest of the house set: 3/.029 single core for lighting, 4mm single core for the AC points, 6mm single core for the earth — all under general wiring.

Frequently asked

Ghar ki wiring ke liye kaun sa wire behtar hai?
Roshni aur pankhon ke liye 1.5 mm² (3/.029), socket aur kitchen ke liye 2.5 mm² (7/.029), har AC point ke liye 4 mm² (7/.036) apne alag 20 A MCB par, aur meter se board tak 6–10 mm². Wire single-core copper ho, poora gauge ho, aur size circuit ke hisaab se ho — brand ka naam in numbers ko nahin badalta.
Is 3/29 wire enough for socket circuits?
No. 3/.029 measures 1.28 mm² of copper — under a true 1.5 mm² — and is rated 19.5 A clipped direct at 30°C. Under a 16 A socket breaker, conduit and summer derating eat the margin. Keep 3/.029 on 6–10 A lighting circuits and run sockets on 7/.029, which measures 3.0 mm² and is rated 27 A. The full comparison is in the 3/29 vs 7/29 guide.
Should house wiring be solid or stranded wire?
Either carries the same rated current at the same size; the difference is workability. Stranded — the 3/29 and 7/29 family — pulls through conduit bends easily and is the default Pakistani house wire. Solid holds its shape in screw terminals and suits short, straight lighting runs. Fine-stranded flexible pulls easiest of all, but its strands need twisting or a ferrule at every termination.
What size is the main wire from the meter to the distribution board?
6–10 mm² copper — 7/.044 or 7/.052 in trade codes, rated 46 A and 63 A clipped direct. Two 1.5 ton ACs draw 16.4 A and a 3 kW geyser 13.6 A — 30 A before a light is counted — which is why the marla guides put 10 mm² on the meter run. Have the electrician total your load and set the main switch under the cable's derated capacity.
Copper or aluminium wire for house wiring?
Copper, at house-circuit sizes. Aluminium earns its place on service drops and long feeders at much larger sizes, where its light weight pays. On the small terminals inside switches, sockets and domestic boards, copper terminates more reliably, and a smaller copper size carries the same current. Every size on this page is a copper size.
Which company's wire is best for house wiring?
Judge the coil, not the slogan: full-gauge strands you can measure with a vernier, bright pure copper, an honest 90 m length, and the correct size for each circuit. Any coil that passes those checks will wire a house properly. How the companies compare on those same tests — and what buying factory-direct changes — is on the best cable company page.
How much wire does a full house need?
It depends on the plot, and each plot size has a worked list: a single-storey 5 marla takes about 21 coils, with the counts for 3 marla, 7 marla, 10 marla and 1 kanal in their own guides. The method behind the numbers is on house wiring cable quantities.

The whole house set, at the factory rate

We draw the copper in Lahore and sell it at the day's rate — no dealer margin, and the line that made the coil answers the message. Send your circuit list and city: Punjab in 1–2 days, rest of Pakistan in 2–4.

WhatsApp for a quote